Siemens SICAM RTUs SM-2556 COM modules (firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00) suffer from authentication bypass, code execution, and cross site scripting vulnerabilities.
6864e041ea9ea5c47eae9ce0c17da621296c15e9daa9c14e95a469ba65d9f5db
SEC Consult Vulnerability Lab Security Advisory < 20171114-0 >
=======================================================================
title: Authentication bypass, cross-site scripting & code
execution
product: Siemens SICAM RTUs SM-2556 COM Modules
(firmware variants ENOS00, ERAC00, ETA2, ETLS00,
MODi00 and DNPi00
vulnerable version: FW 1549 Revision 07
fixed version: none, see Workaround section below
CVE number: CVE-2017-12737 (authentication bypass)
CVE-2017-12738 (XSS)
CVE-2017-12739 (web server)
impact: critical
homepage: www.siemens.com
found: 2017-08-17
by: SEC Consult Vulnerability Lab
An integrated part of SEC Consult
Bangkok - Berlin - Linz - Luxembourg - Montreal - Moscow
Kuala Lumpur - Singapore - Vienna (HQ) - Vilnius - Zurich
https://www.sec-consult.com
=======================================================================
Vendor description:
-------------------
"Siemens is a global powerhouse focusing on the areas of electrification,
automation and digitalization. One of the world's largest producers of
energy-efficient, resource-saving technologies, Siemens is a leading supplier
of systems for power generation and transmission as well as medical diagnosis."
Source: https://www.siemens.com/global/en/home/company/about.html
Business recommendation:
------------------------
SEC Consult recommends not to use this device in production until a thorough
security review has been performed by security professionals and all
identified issues have been resolved. The device must not be accessible from
untrusted networks.
Vulnerability overview/description:
-----------------------------------
1) Authentication Bypass (client-side "authentication" enforcement)
The web interface (TCP port 80) suffers from an authentication bypass
vulnerability that allows unauthenticated attackers to access arbitray
functionality and information (i.e. password lists) available through
the webserver.
2) Reflected Cross-Site Scripting
The web interface provides a "ping" functionality. This form is
vulnerable to reflected cross-site-scripting because of missing input
handling and output encoding.
3) Outdated Webserver (GoAhead)
The used webserver version contains known weaknesses.
Proof of concept:
-----------------
1) Authentication Bypass
Use a browser which has JavaScript disabled ("Authentication" checks are
performed client-side) and open legitimate URLs directly.
Examples:
http://<hostname>/start.asp
http://<hostname>/pwliste.asp
http://<hostname>/goform/webforms_readmem?start_addr=0&length=100
2) Reflected Cross-Site Scripting
All parameters in "webforms_ping" are vulnerable to reflected XSS:
http://<hostname>/goform/webforms_ping?ip_address=1.1.1.com%3Cscript%3Ealert(%27XSS%20proof-of-concept%27)%3C/script%3E1&length_data=32&count_pings=4&timeout=1
3) Outdated Webserver
The used version of "GoAhead" webserver is 2.1.7 (released in Oct. 2003)
This version has known vulnerabilities:
http://aluigi.altervista.org/adv/goahead-adv3.txt
https://web.archive.org/web/20080314153252/http:/data.goahead.com:80/Software/Webserver/2.1.8/release.htm#bug-with-urls-like-asp
Vulnerable / tested versions:
-----------------------------
SM-2556 COM Modules with the firmware variants ENOS00, ERAC00,
ETA2, ETLS00, MODi00 and DNPi00
(FW 1549 Revision 07)
Vendor contact timeline:
------------------------
2017-09-25: Encrypted advisory sent to Siemens ProductCERT
2017-10-02: Requesting status update.
2017-10-09: Vendor states that the "affected device is out of service"
and provides workaround (disable webserver). They are
"still assessing the next steps".
2017-11-02: Requesting status update.
2017-11-06: Siemens ProductCERT will reach out to development team and keep us
posted.
2017-11-08: Siemens ProductCERT prepares advisory.
2017-11-08: Asking about planned release date.
2017-11-13: Siemens ProductCERT provides planned release date (2017-11-14)
2017-11-14: Coordinated public release.
Solution:
---------
No firmware update is available as the device is no longer supported by
the vendor.
Workaround:
-----------
According to the vendor the webserver can be disabled to mitigate all
the vulnerabilities documented in this advisory.
The webserver is optional and only used for commissioning and debugging
purposes.
The vendor published the following document for further information:
https://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-164516.pdf
Advisory URL:
-------------
https://www.sec-consult.com/en/vulnerability-lab/advisories/index.html
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
SEC Consult Vulnerability Lab
SEC Consult
Bangkok - Berlin - Linz - Luxembourg - Montreal - Moscow
Kuala Lumpur - Singapore - Vienna (HQ) - Vilnius - Zurich
About SEC Consult Vulnerability Lab
The SEC Consult Vulnerability Lab is an integrated part of SEC Consult. It
ensures the continued knowledge gain of SEC Consult in the field of network
and application security to stay ahead of the attacker. The SEC Consult
Vulnerability Lab supports high-quality penetration testing and the evaluation
of new offensive and defensive technologies for our customers. Hence our
customers obtain the most current information about vulnerabilities and valid
recommendation about the risk profile of new technologies.
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Interested to work with the experts of SEC Consult?
Send us your application https://www.sec-consult.com/en/career/index.html
Interested in improving your cyber security with the experts of SEC Consult?
Contact our local offices https://www.sec-consult.com/en/contact/index.html
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Mail: research at sec-consult dot com
Web: https://www.sec-consult.com
Twitter: https://twitter.com/sec_consult
EOF SEC Consult Vulnerability Lab / @2017